Allen Bradley Non-Reversing Starter w/ 1 Aux Contact and W56 Heater, 509-COD
PN: 509-COD
- Number of indicator lights: 0
- Voltage type for actuating: AC
- With transformer: No
- Suitable for emergency stop: Yes
- External reset possible: Yes
- With short-circuit release: Yes
- Rated control supply voltage at AC: 50 Hz 110 V
- Rated control supply voltage at AC: 60 Hz 120 V
- Release class: CLASS 30
- Service limit current rating: 52 A
- Continuous current: 45 A
- Circuit closing inrush current peak including offset, max: 483 A
- Operating volt amperes burden Sealed: 38VA, 60 Hz coils (4...5 poles)
- Hp rating, max: 7-1/2 Hp @ 230V load voltage, 1-phase (non-plugging and non-jogging duty)
- Transformer primary switching kVA rating: 8.9 kVA @ 575V load voltage, 3-phase (inrush current = 20...40 times continuous current)
- Temperature compensated overload protection: Yes
- Coordination class according to IEC 60947-4-3: Class 2
- Type of electrical connection of main circuit: Screw connection
- Type of electrical connection for auxiliary- and control current circuit: Screw connection
- Rail mounting possible: Yes
- Maximum number of auxiliary contacts: 8
- Average operating time, pick-up: 27 ms
- Average operating time, drop-out: 13 ms
- Required torque on power terminal wire clamps and pressure connectors or lugs: 45 lb. inch
- Auxiliary contact material: Silver
- Type of power terminal: Pressure terminals
- Wire size For power terminals: 14...4 AWG
- Enclosure: Open type
- Power contact material: Silver Alloy
- Requirements for sizing of wire: All wire rated 167 °F (75 °C) or higher must be sized per the local electrical code for 167 °F (75 °C) wire
- NEMA size: Size 2
- Operating temperature: 65 °C
- Operating position: Vertical
- Overload relay: Eutectic alloy overload relay
- Corrosion-resistance: All metal parts are treated for corrosion-resistance