Product Description
Honeywell Ultraviolet Flame Amplifier R7849A1023
PN: R7849A1023
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules
Tech Specs
Features:
Flame failure response time of 0.8 or 3.0 seconds.
Flame signal strength ranges from 0.0 to 5.0 Vdc.
Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
Flame signal test jacks to measure amplifier flame signal voltage.
Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
Compatible with existing Honeywell flame detectors (order separately).
Type: Ultraviolet
Flame Failure Response Time (sec): 2.0 sec or 3.0 sec
Self Checking: None (standard)
Use With Primary Safety Control: 7800 SERIES Relay Modules