Product Description
Armstrong GP-2000 Pressure Reducing Valve
PN: D25623
The GP-2000 is a high-performance, externally piloted reducing valve for steam service with large-capacity requirements. Typical use is on intermittent service, including applications such as heat exchangers, steam coils, rotating dryers, process equipment and heating systems. With a 20:1 rangeability and high Cv, the GP-2000 is reliable and accurate (+/-1% of pressure set point from 5% to 100% of flow) over a long, trouble-free service life. Hardened stainless steel working parts are renewable in-line. The GP-2000 is single-seated for dead-end service.
- Model: GP-2000 Integral or Remote Pilot
- Fluid: Steam
- Connection Type: Flanged ANSI 150#
- Spring Color: Green
- Max. Inlet Pressure: 185 psig, 13 bar
- Pressure ( Green): 15~157 psig, 1-11 bar
- Body: Ductile Iron