Product Description
Allen Bradley 104-C30EJ22 IEC 30 A Reversing Contactor
PN: 104-C30EJ22
- Voltage type for actuating: DC
- Rated control supply voltage at DC: 24 V
- Current (Ie), max: 97 A
- Switching frequency, max: 200 ops/h
- Main current circuit resistance: 2 mohm
- Cross section per UL/CSA: 16
- Rated operational current for contactor at elevator duty (UL/CSA): 27.0A @ 460V
- Rated operational power for contactor at elevator duty (UL/CSA): 7.5Hp @ 230V
- Rated isolation voltage (Ui): 690V @ IEC
- Rated voltage (Ue): 690V @ AC, 50/60 Hz
- Rated operational power for contactor at wye-delta: 30Hp @ 575V, 60 Hz
- Rated filament current: 30A @ 230/240V, AC-5b
- Power dissipation: 5.4 W @ 400V, AC-3, Ie
- Coil terminal conductor cross section: 1…4 mm² @ 2 conductor
- Rated current (enclosed): 28A @ 230V, 1-phase per UL/CSA
- Rated power (enclosed): 7.5Hp @ 200V, 3-phase per UL/CSA
- Coil consumption pick-up (avg/peak): 14/22 W @ DC (electronic-EA)
- General purpose current (enclosed): 55 A per UL/CSA
- Capacitance, max: 540 µF @ short-circuit current of 50 kA
- Switching of low inductive loads: 45A @ 440V, AC-7a per IEC 61095 (50 Hz)
- Operating limits, pick-up: (0.85...1.1) x Us @ 50 Hz, 60 Hz, 50/60 Hz
- Switching of motor load: 30A @ 400V, AC-7b per IEC 61095 (50 Hz)
- Short time withstand (Icw): 300A @ 10s, 60 °C
- Coil consumption, hold-in: 3 W @ DC (electronic-EA)
- Coil consumption, pick-up: 105VA @ 50 Hz, 60 Hz, 50/60 Hz
- Operating time: 20…50 ms @ DC (electronic) opening delay
- Total power dissipation DC control (electronic): 7.1 W @ 400V, AC-3, Ie
- Operating limits, dropout: (0.3...0.6) x Us @ 50 Hz, 60 Hz, 50/60 Hz
- Switching of lamps Gas discharge lA, open: 40.5A @ 40°C (104 °F), AC-5a
- Switching of hermetically sealed cooling compressor motors: 38A @ 500V, AC-8a (manual reset of overload release (50 Hz))
- Coil insulation class: Class F per IEC 60085, UL Class 105
- Rating for switching AC motors 3-poles: 7.5Hp @ 200V (AC-2, AC-3, AC-4), 3-phase (60 Hz)
- BS88 fuses current rating: Type 2 (per IEC 60947-4-1): 63A @ 415V, 65 kA available fault current
- UL class K5 and RK5 fuses rating: 110A @ 600V, 5 kA available fault current per UL 508 and CSA 22.2 No. 14
- UL inverse-time circuit breaker: 50 A @ 600Y/347V @ 25kA available fault current per UL 508 and CSA 22.2 No. 14
- Coil voltage: 24V DC with electronic coil
- Rated operational current (Ie): 65A @ 690V, AC-1 active power load (50 Hz), ambient temperature 60 °C
- Rated operational power (Pe): 78 kW @ 690V, AC-1 active power load (50 Hz), ambient temperature 60 °C
- DIN fuses (gG, gL) current rating Type 2 (per IEC 60947-4-1): 80A @ 690V, 50 kA available fault current
- UL class J and CSA HRCI-J fuses rating: 50A @ 100kA available fault current per UL 508 and CSA 22.2 No. 14
- Switching of power transformers: Apparent power: 8.3 kVA @ 240V, AC-6a 60 Hz (n = 30)
- Switching of 3-phase Capacitors: Single capacitor: 20 kVAR @ 690V, AC-6b 50 Hz, 60 °C (Inductance of leads between capacitors in parallel: min. 6 µH)
- Switching of DC loads: 3-Poles in series: 45A @ 48/60V (Shunt-wound motors starting, reverse current braking, reversing, stepping DC-3 at 60 °C)
- Contacts: 3 power poles with internal NO or NC auxiliary contact or 4 power poles (9...23 A), Optional front-or side mounted 1-2 or 4-pole external auxiliary contact block
- Function: Reversing contactor
- Rated impulse voltage withstand (Uimp): 6 kV
- Conventional coil type: True
- Electronic-EI coil type: True
- Rated coil frequency: AC 50/60 Hz, DC
- Ripple, max: ±15% @ DC (electronic)
- OFF time, min: 50 ms @ DC (electronic)